Product Description AC600 series high performance universal inverter single 3 phase frequency invt 7.5/11Kw The AC600 uses a DSP control system,to Realize vector control without velocity sensor,effectively suppressing low frequency oscillations;Abundant terminals make the application more flexible.It is mainly applied to fan and pump loads and has high requirements on speed control accuracy, torque response speed and low frequency output.
Package: Standard carton package/wooden case Shipment: By sea,By air,by express like DHL,FedEX It is used in dive automation production,involving wire drawing machine, film winding, coating machine, CNC machine tools, weaving machines, jacquard machines, fans, pumps, chemical fiber, textile, synchronous interaction, injection molding machines, lifting, elevator, machine tools, rolling mills, tube wire processing, lifting, lifting equipment, mill. Q:what's your delivery time? A:3-5 working days for small order ,10-15 working days for big order. Q:what's your warranty term? A:we offer 24 months warranty time. Q:Could you sell spare parts? A if you are using our product.we can sell spare parts to you.but we couldn't sell the half-finished products. Q:Can you make the inverter and soft starter control board(switchgear)? A: YES,we have a lot of experience in design frequency inverter and soft starter cabinet according to your request,these items be produce by ourselves from our factory. Q:How does your factory control the quality? A:Quality is priority, we always attach importance to quality control from the beginning to the end of production,every product willl be fully assembled and carefully tested before packing and shipping. Q:how can i trust you ? A our company has been audited and approved ISO9001,CE,CCC,Assessment report will be sent to you by Email.And we will take all the responsibility once problem during warranty time. Contact us |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Type | Terminal | Name | Function Description |
Power Supply | +10V-GND | External +10 V power supply |
Provide +10 V power supply to external unit. Generally, it provides power supply to external potentiometer with resistance range of 1-5kΩ. Maximum output current:10mA |
+24V-COM | External +24 V power supply |
Provide +24 V power supply to external unit. Generally, it provides power supply to DI/DO terminals and external sensors. Maximum output current:200mA |
|
Analog Input | AI1-GND | Analog input 1 | Input voltage range: 0-10 VDC Impedance: 22kΩ |
AI2-GND | Analog input 2 | Input range: 0-10 VDC/0-20mA, decided by jumper J1 on the control board Impedance: 22kΩ (voltage input),500 Ω (current input) |
|
Digital input | DI1- COM | Digital input 1 | Optical coupling isolation Impedance: 2.4kΩ Voltage range for level input: 9-30V |
DI2- COM | Digital input 2 | ||
DI3- COM | Digital input 3 | ||
DI4- COM | Digital input 4 | ||
DI5- COM | High-speed pulse input |
Besides features of DI1-DI4, it can be used for high-speed pulse input. Maximum input frequency: 100 kHz |
|
Analog output | AO1-GND | Analog output 1 | Voltage or current output is decided by jumper J2. Output voltage range: 0-10V Output current range: 0-20mA |
Digital output | DO1-COM | Digital output 1 | Optical coupling isolation, dual polarity open collector output Output voltage range: 0-24V Output current range: 0-50mA |
FM- COM | High-speed pulse output |
It is limited by P5-00 (FM terminal output mode selection). As high-speed pulse output, the maximum frequency hits 100 kHz. As open-collector output, its specification is the same as that of DO1 |
|
Relay Output | T/A-T/B | NC terminal | Contact driving capacity: 250VAC, 3A, COS ø=0.4 30VDC, 1A Applying to Overvoltage Category II circuit |
T/A-T/C | NO terminal | ||
Auxiliary interface |
J3 | 485 communication |
Jumper selection to decide whether to connect 330Ω matched resistor to make 485 communication |
J5 | External operation panel interface |
Connect to external operation panel. |