AC drive model | Power capacity(kVA) | Input current A | Output current A | Adaptable Motor | |
AC9002T45GB | 69 | 92 | 91 | 45KW,60HP |
Model | Mounting Hole | Overall Dimension(mm) | Mounting hole Diameter(mm) | Weight(kg) | ||||
A | B | H | H1 | W | D | |||
AC9002T45GB | 260 | 580 | 549 | 600 | 385 | 265 | Φ10 | 32 |
AC drive | Power capacity(kVA) | Input current A | Output current A | Adaptable Motor KW. HP |
|
Single-phase power :220V,50/60HZ | |||||
AC900-S0.75GB | 1.5 | 8.2 | 4.0 | 0.75 | 1 |
AC900-S1.5GB | 3.0 | 14.0 | 7.0 | 1.5 | 2 |
AC900-S2.2GB | 4.0 | 23.0 | 9.6 | 2.2 | 3 |
Three-phase power:220V,50/60Hz | |||||
AC900-2T4.0G | 3 | 5 | 3.8 | 0.75 | 1 |
AC900-2T5.5G | 4 | 5.8 | 5.1 | 1.5 | 2 |
AC900-2T7.5G | 5.9 | 10.5 | 9 | 2.2 | 3 |
AC900-2T11G | 8.9 | 14.6 | 13 | 3.7 | 5 |
AC900-2T15G | 17 | 26 | 25 | 5.5 | 7.5 |
AC900-2T18.5G | 21 | 35 | 32 | 7.5 | 10 |
AC900-2T22G | 30 | 46.5 | 45 | 11 | 15 |
AC900-2T30G | 40 | 62 | 60 | 15 | 20 |
AC900-2T37G | 57 | 76 | 75 | 18.5 | 25 |
AC900-2T45G | 69 | 92 | 91 | 22 | 30 |
AC900-2T55G | 85 | 113 | 112 | 30 | 40 |
AC900-2T75G | 114 | 157 | 150 | 37 | 50 |
AC900-2T90G | 134 | 180 | 176 | 45 | 60 |
AC900-2T110G | 160 | 214 | 210 | 55 | 75 |
AC900-2T132G | 231 | 307 | 304 | 75 | 100 |
Type | Terminal | Name | Function Description |
Power Supply | +10V-GND | External +10 V power supply |
Provide +10 V power supply to the external unit. Generally, it provides power supply to external potentiometer with the resistance range of 1-5kΩ. Maximum output current:10mA |
+24V-COM | External +24 V power supply |
Provide +24 V power supply to the external unit. Generally, it provides power supply to DI/DO terminals and external sensors. Maximum output current:200mA |
|
Analog Input | AI1-GND | Analog input 1 | Input voltage range: 0-10 VDC Impedance: 22kΩ |
AI2-GND | Analog input 2 | Input range: 0-10 VDC/0-20mA, decided by jumper J1 on the control board Impedance: 22kΩ (voltage input),500 Ω (current input) |
|
Digital input | DI1- COM | Digital input 1 | Optical coupling isolation Impedance: 2.4kΩ Voltage range for level input: 9-30V |
DI2- COM | Digital input 2 | ||
DI3- COM | Digital input 3 | ||
DI4- COM | Digital input 4 | ||
DI5- COM | High-speed pulse input |
Besides features of DI1-DI4, it can be used for high-speed pulse input. Maximum input frequency: 100 kHz |
|
Analog output | AO1-GND | Analog output 1 | Voltage or current output is decided by jumper J2. Output voltage range: 0-10V Output current range: 0-20mA |
Digital output | DO1-COM | Digital output 1 | Optical coupling isolation, dual polarity open collector output Output voltage range: 0-24V Output current range: 0-50mA |
FM- COM | High-speed pulse output |
It is limited by P5-00 (FM terminal output mode selection). As high-speed pulse output, the maximum frequency hits 100 kHz. As open-collector output, its specification is the same as that of DO1 |
|
Relay Output | T/A-T/B | NC terminal | Contact driving capacity: 250VAC, 3A, COS ø=0.4 30VDC, 1A Applying to Overvoltage Category II circuit |
T/A-T/C | NO terminal | ||
Auxiliary interface |
J3 | 485 communication |
Jumper selection to decide whether to connect 330Ω matched resistor to make 485 communication |
J5 | External operation panel interface |
Connect to external operation panel. |